This Frequently Asked Questions (FAQ) list includes questions
and answers from various sources, including Labs21 partner projects,
Labs21
supporters,
laboratory
design experts, and others. The questions are categorized by strategy.
This list is continually updated. If you would like to contribute
to
it, please contact
us.
Energy Recovery
Q. What are the typical O&M procedures
for run-around glycol loops? Are there particular design strategies
to minimize O&M requirements?
Q. Can energy recovery wheels be used
in chemistry labs?
Optimize Ventilation Requirements
Q. Our university campus standard is 10
ACH ventilation rate for laboratories. How do I address safety
concerns when lowering
the required minimum ventilation rate to 8 ACH or even 6 ACH?
Efficient Fume hoods
Q. You claim improved safety and performance
of lower velocity fume hoods such as the Berkeley Hood. Our
Safety Office is not
convinced about the benefits of speeds below the standard 100
fpm. Can you provide any technical papers to support the lower
velocity designs?
Q. Our lab needs a small stand-alone
hood for storing H2S (and other toxic gas) cylinders. What
you recommend?
Rightsizing Laboratory Equipment Load
Q. The Labs21 EPC Energy Credit
9 requires that electrical panels be designed to allow for
portable or permanent check metering
of equipment loads. How much space is required in the panel to
allow for clamp on meters? What type of meters can be used?
Q. What are the typical
O&M
procedures for run-around glycol loops? Are there particular
design strategies to minimize
O&M
requirements?
A. The O&M is typical to any hydronic and coil system - glycol
needs to be annually checked and periodically replaced, pumps need
minimal maintenance, system performance needs to be checked and
optimized, and coils need to be cleaned if pressure drop starts
to increase across coils.
Filters should be installed before supply
and exhaust coils. If corrosive conditions are expected use a
coil coating to minimize
corrosion on the exhaust coil. The filters can be low efficiency
- they are there mostly to catch things like wipes that get sucked
into
the exhaust system. Be sure to design to allow filer replacement
without having to enter the exhaust stream.
Q. Can energy recovery wheels be used in chemistry labs?
A. The concern is always cross-contamination, although it can
be minimized with advanced
membranes, seal design, and seal pressurization.
Enthalpy wheels have been used in many bio labs (see Labs21 case
studies of NIH, Pharmacia and Nidus Center) and some chemistry
labs. The reason they are considered better for bio labs is that
bacteria and viruses are relatively big - the smallest virus is
about 3000 angstroms and the pore size on an enthalpy wheel is
3 A, so they cannot be transferred in the pore. Also biology work
is typically done in a BSC that has a HEPA filter on the exhaust,
so in theory no biologicals ever leave the lab. If for some reason
biologicals did leave the BSC and did somehow get transferred
on the wheel, the supply air to a bio lab is usually also HEPA
filtered, so they would get caught there.
Enthalpy wheels have been used in chemistry labs. The best example
is Johns Hopkins Ross Research building. They have 164 fume hoods,
150 BSCs and general exhaust. All exhaust goes through the wheels.
However, in most cases, EHS officers will not allow fume hood exhaust
to
go through the wheel. In such cases, it may not be effective
to use a wheel, since chemistry lab exhausts are often fume hood
driven.
Q. Our university campus standard is 10 ACH ventilation
rate for laboratories. How do I address safety concerns when
lowering
the required minimum ventilation rate to 8 ACH or even 6 ACH?
A. Ask your EHS professional for the scenario when 10
air changes are safe and 6 air changes are not. Generally the concern
is a major release such as a spill. In such a situation, neither
air change rates are safe - the occupants should leave. So if they
have the opportunity to push a panic switch, five benefits can
arise:
1. The control system can increase the airflow significantly (say
to 20+ air changes)
2. An alarm can signal your EHS staff that there is a problem
3. An alarm can signal others that may enter the lab that they
should not
4. Huge amounts of energy and capital costs are not wasted
5. Lower quantities of air supply reduce the negative effects supply
air can have on fume hoods
This option with lower capital and operating cost
may actually significantly improve safety.
Many labs are not classified as hazardous (most university labs).
H-6 occupancy (a hazardous classification) only requires six air
changes. Note that standards are not codes,
and judgment is required in their application. For example, ASHRAE's
recommendation of 6 to 12 air changes does not mean 6 is marginal
and 12 is better. There are many examples when more air is not
better (e.g. fume hood face velocity).
It is when a
systems approach is not used that air change rates may be driven
up. Poor design may lead to more airflow. For example, if the
room airflow patterns are not well designed, undesirable dead air
spaces may occur. Increasing airflow and turbulence solves that
design problem, but can significantly undermine the safety of the
fume hoods. A systems approach optimizes all aspects (no dead air,
and safe hoods) and is a win-win approach.
If a 200,000 square foot lab saves 4 air changes that would be
in the ball park of $800K per year (perhaps more in colder/warmer
climates). That could pay for a full time energy manager and a
full time EHS
manager to optimize and assure long term performance while still
putting hundreds of thousands of dollars back into research or
teaching.
Q. You claim improved safety
and performance of lower velocity fume hoods such as the Berkeley
Hood. Our Safety Office
is
not convinced about the benefits of speeds below the standard 100
fpm. Can you provide any technical papers to support the lower
velocity designs?
A. 100 fpm is the optimum face velocity for most hoods (conventional
design). However, there are a number of manufacturers developing
high performance hoods that require less air flow and maintain
or enhance containment/safety. Such is the case with the Berkeley
push-pull hood (http://ateam.lbl.gov/hightech/fume hood/fhood.html)
These two recent reports compare a very high performing
conventional hood to the Berkeley Hood using both a standard testing
protocol and a new dynamic test.
- Comparison with standard protocol
- Comparison with dynamic test
As can be seen, the
Berkeley hood running at 50% of the air volume performed significantly
better than the conventional hood (running at 100 fpm) in side
by side tests.
There are some in the industry who do not favor high performance
hoods (e.g. manufacturers without competitive products, and hood
control vendors worried that high performance, constant volume
hoods may become competition to their products), so you should
be skeptical of the nay- sayers. However, you should be equally
cautious about "high
performance" hoods that aren't high performance. The bottom
line is that hood performance should be judged using industry standard
tests on hoods as-installed (not as manufactured in an ideal test
chamber). Containment is far more important than face velocity.
We strongly advocate automated hood controls (e.g. VAV), room
pressure controls, monitoring and alarms (for any hood/lab).
A growing number of experts believe that face velocity is not
a good indicator of containment or safety. 12.5% to 17%
of installed hoods with 100 fpm face velocity fail more robust
tracer
gas testing (ASHRAE 110 using ANSI/AIHA thresholds). Therefore
there is growing consensus that to assure safety, containment testing
must be performed (i.e. ASHRAE 110).
The Berkeley Hood is in the field testing and demonstration phase.
We are running these tests at 50% of conventional air flow. Our
ultimate
goal is a safer hood running at 25 to 30 percent of the airflow
used in conventional hoods. Other high performance hoods are on
the market. Generally they operate at 60 to 80 percent of the traditional
air volume. These, often safer hoods, should be considered for
projects now. Some can be combined with VAV and other control strategies
and, if required, they can be run at higher flows to satisfy arbitrarily
set standards. If lower flows are accepted, the savings in the
HVAC system can more than pay for the higher cost of the hood and
the testing. The end result is lower first cost, lower operating
costs, and improved safety.
Reducing the face velocity does reduce turbulence and eddies in
front of the user. The Berkeley Hood actually introduces air
at the face of the hood (in front of the user), thus further eliminating
such
problems. The reduction of turbulence and eddies near the face
of a hood is a side benefit of high performance hoods and may be
most beneficial in high density fume hood situations, such as teaching
labs, where it is very difficult to design the supply/make-up air
system to not interfere with the performance of the hoods. Unfortunately
cross currents can have a greater impact on some low flow hoods,
especially more conventional hoods running at low face velocities.
This underscores the benefit of as-installed testing of the hoods
within the context of an overall system.
Q. Our lab needs a small stand-alone hood for storing
H2S (and other toxic gas) cylinders. What you recommend?
A. We recommend not using a lab hood to store gas cylinders. You
should use a gas cabinet. They will use less energy and provide
a higher degree of safety.
Q. The Labs21 EPC Energy
Credit 9 requires that electrical panels be designed to allow
for portable or permanent check metering
of equipment loads. How much space is required in the panel to
allow for clamp on meters? What type of meters can be used?
A. The usual configuration puts the current transformers and voltage
connections inside the panel, and the actual logger is outside
the panel. This requires the wires to run out through a partially
closed door. Most authorities
allow this configuration for temporary connections, and typically
no
special provision needs to be made for it (the CTs and voltage
connections coexist with what's in the panels already). If one
insists on having the panel cover completely secured, then the
logger needs to be inside, and it either needs to run on its batteries
or the low-voltage power supply needs to somehow be provided inside
the panel. Most panels have enough extra room for the latter configuration,
but a really packed panel might not.
Examples of loggers which are commonly used these days
for energy logging field work are the Elite Pro units with split-core
CTs (technically a clamp-on is a hand-held device). See these logger
specifications and CT
specifications.
|